20 Amp

35 AMP

50/60 AMP

80 AMP

100/150 AMP

20 AMP MERCURY RELAYS

 

Coil Voltage: Standard voltages of 24V and 120V 50/60 Hz and 24V DC. Two and 3 pole coils in series.
Contact Load: For highly inductive and DC loads contact Mercury Switches Inc.
Pull-in Voltage: Typically less than 80% of nominal.
Drop-out Voltage: Approximately 4 volts less than pull-in voltage.
Timing: Contact closing or opening from 50 to 100 milliseconds.
Contact Resistance: Typically .005 Ohm.
Dielectric Withstand: 2500V R.M.S.
Life Expectancy: In excess of 1 million under normal conditions of temperature and load.
Temperature Range: -35 to +75 deg. C
Termination: 1/4" quick connect terminals.
U.L. Standard: Meets or exceeds UL & CSA requirements.

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

24NO-24A

20 Amp 120V AC Resistive ONLY
10 Amp 120V AC Tungsten lamp.

24V 50/60 Hz

185 mA

2.0W

S.P.S.T.N.O.

224NO-24A

24V 50/60 Hz

380 mA

4.4W

D.P.S.T.N.O.

324NO-24A

24V 50/60 Hz

675 mA

8.5W

T.P.S.T.N.O.

24NO-120A

120V 50/60 Hz

45 mA

2.2W

S.P.S.T.N.O.

224NO-120A

120V 50/60 Hz

78 mA

5.4W

D.P.S.T.N.O.

324NO-120A

120V 50/60 Hz

145 mA

9.2W

T.P.S.T.N.O.

20 Amp

35 AMP

50/60 AMP

80 AMP

100/150 AMP

35 AMP MERCURY CONTACTORS

Coil Voltage: Standard voltages of 24, 120, 208/240, 277 and 480V 50/60 Hz and 24V DC. Other voltages on request.
Contact Load: For highly inductive and DC loads specify "H" units.
Pull-in Voltage: Under 90 volts for 120V 50/60 Hz. Typically less than 70% of nominal.
Drop-out Voltage: Approximately 2 volts less than pull-in voltage.
Timing: Contact closing or opening from 50 milliseconds.
Contact Resistance: Typically .003 Ohm.
Dielectric Withstand: 2500V R.M.S.
Life Expectancy: Mechanical - 25 million; Resistive Load - 5 million; Tungsten Lamp - 10,000 minimum.
Max. Load Cycling: 20 times per minute at 23 deg. C ambient (reduced life).
Temperature Range: -35 to +75 deg. C
Termination: Coil with #6 binding head screw. Load terminals with pressure connector for AWG #6-14 leads. Alternate terminals as shown on "T" units
Standard Listing: UL listed as Industrial Control Equipment E76691 (N). CSA 56002. Approval for 100,00 cycles endurance test. Temperature tested at 140 deg. F ambient. Undervoltage and increased voltage tests at 18 and 31V AC respectively for 24V AC coils.

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

35NO-120AH

35 Amp 480V AC General purpose
35 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

40 mA

2.5W

S.P.S.T.N.O.

235NO-120AH

120V 50/60 Hz

80 mA

5W

D.P.S.T.N.O.

335NO-120AH

120V 50/60 Hz

120 mA

7.5W

T.P.S.T.N.O.

35NC-120AH

120V 50/60 Hz

55 mA

3W

S.P.S.T.N.C.

235NC-120AH

120V 50/60 Hz

110 mA

6W

D.P.S.T.N.C.

335NC-120AH

120V 50/60 Hz

165 mA

9W

T.P.S.T.N.C.

For 35NO U.L. & CSA Rating: 35 Amp 600V AC Resistive (reduced life).



"T" Termination
Shown with 1/4" allen cap screws



"t" Termination
Shown with 8-32 binding head screws

Units are functionally identical to 35NO/35NC series. Catalog numbers with suffix T, for example: 35NO-120AT, are with 1/4" allen cap screws. Numbers with suffix t, for example: 35NO-24At, are with 8-32 binding head screws for ring or spade terminals. T terminals receive AWG #8-14 leads.

20 Amp

35 AMP

50/60 AMP

80 AMP

100/150 AMP

50/60 AMP MERCURY CONTACTORS

Coil Voltage: Standard voltages of 24, 120, 208/240, 277 and 480V 50/60 Hz and 24V DC. Other voltages on request.
Contact Load: For highly inductive and DC loads specify "H" units.
Pull-in Voltage: Under 90 volts for 120V 50/60 Hz. Typically less than 70% of nominal.
Drop-out Voltage: Approximately 2 volts less than pull-in voltage.
Timing: Contact closing or opening from 50 milliseconds.
Contact Resistance: Typically .002 Ohm.
Dielectric Withstand: 2500V R.M.S.
Life Expectancy: Mechanical - 25 million; Resistive Load - 5 million; Tungsten Lamp - 10,000 minimum.
Max. Load Cycling: 20 times per minute at 23 deg. C ambient (reduced life).
Temperature Range: -35 to +75 deg. C
Termination: Coil with #6 binding head screw. Load terminals with pressure connector for AWG #2-12 leads.
Standard Listing: UL listed as Industrial Control Equipment E76691 (N). CSA 56002. Approval for 100,00 cycles endurance test. Temperature tested at 140 deg. F ambient. Undervoltage and increased voltage tests at 18 and 31V AC respectively for 24V AC coils.

50 AMP CONTACTOR

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

50NO-120AH

50 Amp 480V AC General purpose
50 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

40 mA

2.5W

S.P.S.T.N.O.

250NO-120AH

120V 50/60 Hz

80 mA

5W

D.P.S.T.N.O.

350NO-120AH

120V 50/60 Hz

120 mA

7.5W

T.P.S.T.N.O.

50NC-120AH

50 Amp 240V AC General purpose
45 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

55 mA

3W

S.P.S.T.N.C.

250NC-120AH

120V 50/60 Hz

110 mA

6W

D.P.S.T.N.C.

350NC-120AH

120V 50/60 Hz

165 mA

9W

T.P.S.T.N.C.

60 AMP CONTACTOR

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

60NO-120AH

60 Amp 480V AC General purpose
60 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

40 mA

2.5W

S.P.S.T.N.O.

260NO-120AH

120V 50/60 Hz

80 mA

5W

D.P.S.T.N.O.

360NO-120AH

120V 50/60 Hz

120 mA

7.5W

T.P.S.T.N.O.

60NC-120AH

60 Amp 240V AC General purpose
50 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

55 mA

3W

S.P.S.T.N.C.

260NC-120AH

120V 50/60 Hz

110 mA

6W

D.P.S.T.N.C.

360NC-120AH

120V 50/60 Hz

165 mA

9W

T.P.S.T.N.C.

20 Amp

35 AMP

50/60 AMP

80 AMP

100/150 AMP

80 AMP MERCURY CONTACTORS

Coil Voltage: Up to 480V AC and 250V DC.
Contact Load: 80 Amp 480V AC Resistive.
Pull-in Voltage: Under 90 volts for 120V 50/60 Hz.
Drop-out Voltage: Approximately 5 volts less than pull-in voltage.
Timing: Contact closing or opening from 70 milliseconds.
Contact Resistance: Typically .001 Ohm.
Dielectric Withstand: 2500V R.M.S.
Life Expectancy: Mechanical - 25 million; Resistive Load - typically 5 million at room temperature and slow operating cycle.
Temperature Range: -35 to +75 deg. C
Termination: Coil with #6 binding head screw. Load terminals with pressure connector for AWG #2-8 leads. (larger size connectors available)

80 AMP CONTACTOR

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

80NO-120AH

80 Amp 480V AC General purpose
80 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

150 mA

8W

S.P.S.T.N.O.

280NO-120AH

120V 50/60 Hz

300 mA

16W

D.P.S.T.N.O.

380NO-120AH

120V 50/60 Hz

450 mA

24W

T.P.S.T.N.O.

80NC-120AH

80 Amp 240V AC General purpose
75 Amp 120V AC Tungsten lamp.

120V 50/60 Hz

225 mA

12W

S.P.S.T.N.C.

280NC-120AH

120V 50/60 Hz

450 mA

24W

D.P.S.T.N.C.

380NC-120AH

120V 50/60 Hz

675 mA

36W

T.P.S.T.N.C.

15 AMP HV CONTACTOR

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

15HVO-120AH

15 Amp 3500V AC Inductive 0.75pf

120V 60 Hz

150 mA

8W

S.P.S.T.N.O.

215HVO-120AH

120V 60 Hz

300 mA

16W

D.P.S.T.N.O.

315HVO-120AH

120V 60 Hz

450 mA

24W

T.P.S.T.N.O.

15HVC-120AH

10 Amp 3500V AC Inductive 0.75pf

120V 60 Hz

225 mA

12W

S.P.S.T.N.C.

215HVC-120AH

120V 60 Hz

450 mA

24W

D.P.S.T.N.C.

315HVC-120AH

120V 60 Hz

675 mA

36W

T.P.S.T.N.C.

15 AMP 3500 VOLT MERCURY CONTACTORS:
The 80 Amp units - modified - are ideal for high voltage application such as UV lamp circuits. Dielectric withstand voltage exceeds 10000 VAC between load terminals and load and coil circuits. Pressure connectors for AWG #4-14 are provided. Dimensional data are identical to the 80 AMP units.

20 Amp

35 AMP

50/60 AMP

80 AMP

100/150 AMP

100/150 AMP MERCURY CONTACTORS

Coil Voltage: Up to 480V AC and 250V DC.
Contact Load: See below.
Pull-in Voltage: Under 90 volts for 120V 50/60 Hz.
Drop-out Voltage: 65% of rated voltage.
Timing: Contact closing or opening between 40 and 90 milliseconds.
Contact Resistance: Typically .001 Ohm.
Dielectric Withstand: 2500V R.M.S.
Life Expectancy: Mechanical - 25 million; Resistive Load - 5 million
Temperature Range: -35 to +70 deg. C

100 AMP CONTACTOR

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

100NO-120AH

100 Amp 480V AC General purpose
100 Amp 120V AC Tungsten lamp.

120V 60 Hz

190 mA

11W

S.P.S.T.N.O.

2100NO-120AH

120V 60 Hz

380 mA

22W

D.P.S.T.N.O.

3100NO-120AH

120V 60 Hz

570 mA

33W

T.P.S.T.N.O.

CONTACT RATING PER POLE (RESISTIVE ONLY)

Volts 60 Hz

Up to 240

277

480

600

Amps

100

100

100

100

150 AMP CONTACTOR

Cat. No.

Load Rating Per Pole

Coil Voltage

Coil Current

Coil Power

Contact

150NO-120AH

150 Amp 120V AC General purpose
120 Amp 120V AC Tungsten lamp.

120V 60 Hz

190 mA

11W

S.P.S.T.N.O.

2150NO-120AH

120V 60 Hz

380 mA

22W

D.P.S.T.N.O.

3150NO-120AH

120V 60 Hz

570 mA

33W

T.P.S.T.N.O.

CONTACT RATING PER POLE (RESISTIVE ONLY)

Volts 60 Hz

Up to 240

277

480

600

Amps

150

140

130

120

20 Amp

35 AMP

50/60 AMP

80 AMP

100/150 AMP

Distributed by: T&C Industrial Controls, Inc.
1121 N. Cedar St. * Glendale, CA 91207 USA
(818) 240-3600 * FAX (818) 547-9359
Email to: tcindust@flash.net

Manufactured by: Mercury Switches, Inc.
3010 Winding Waters * Elkhart, IN 46514
(800) 752-9312 * FAX (219) 262-8327